Numerical Investigation into the Air Flow Distributions of the Air Conditioning System in the Modular Data Center

Numerical Investigation into the Air Flow Distributions of the Air Conditioning System in the Modular Data Center

Year:    2019

Author:    Hao Dong, Ziqiang Qin, Shicheng Liu, Yao Li, Yingying Shen, Haibo Wang, Yitong Zong, Xiaojun Wu, Haiqing Si

Advances in Applied Mathematics and Mechanics, Vol. 11 (2019), Iss. 1 : pp. 91–107

Abstract

Data center plays an increasingly important role in everyday life. As data center is becoming more and more powerful, energy consumption is also increasing dramatically. The air conditioning system occupies at least 50 percent of the total energy consumption. Therefore, delicate analysis on the air conditioning system could help to reduce energy consumption in data center. An advanced Finite Volume Method with RNG $k-\varepsilon$ model and convective heat exchange model is used in this paper to study the airflow and the temperature distribution of modular data center under different arrangements. Specifically, the calculation formula of convective heat transfer coefficient for plate flow is adopted to simplify analysis; and fans on the back of racks are simplified to be walls with a certain pressure jump. Simulations reveal that, in the case where air conditioners are arranged face-to-face, the temperature distribution on the back of racks is not uniform, and local high temperature points emerge near the side wall of air conditioners. By analyzing the distribution of air flow and temperature, geometric model is optimized by using a diagonal rack arrangement and drilling holes on the side wall. In the same energy consumption situation, the overall maximum temperature of the optimized model is reduced by 2.3$^\circ$C compared with that of the original one, and the maximum temperature on the server surface is reduced by 1$^\circ$C. Based on the optimized model, the effect of the hot aisle distance on the temperature distribution is studied. By simulating four different cases with various distances of hot aisle of 100cm, 120cm, 130cm and 150cm, it is found that the temperature is generally lower and distributed more evenly in the case with 120cm hot aisle distance. This demonstrates that the distance of hot aisle has an effect on temperature.

You do not have full access to this article.

Already a Subscriber? Sign in as an individual or via your institution

Journal Article Details

Publisher Name:    Global Science Press

Language:    English

DOI:    https://doi.org/10.4208/aamm.OA-2018-0139

Advances in Applied Mathematics and Mechanics, Vol. 11 (2019), Iss. 1 : pp. 91–107

Published online:    2019-01

AMS Subject Headings:    Global Science Press

Copyright:    COPYRIGHT: © Global Science Press

Pages:    17

Keywords:    Modular data center air conditioning temperature distribution hot/cold aisle CFD.

Author Details

Hao Dong

Ziqiang Qin

Shicheng Liu

Yao Li

Yingying Shen

Haibo Wang

Yitong Zong

Xiaojun Wu

Haiqing Si

  1. The Role of HVAC Design and Windows on the Indoor Airflow Pattern and ACH

    Pirouz, Behrouz | Palermo, Stefania Anna | Naghib, Seyed Navid | Mazzeo, Domenico | Turco, Michele | Piro, Patrizia

    Sustainability, Vol. 13 (2021), Iss. 14 P.7931

    https://doi.org/10.3390/su13147931 [Citations: 21]
  2. Conceptual thermal design for 40 ft container type 3.8 MW energy storage system by using computational simulation

    Kwon, Hwabhin | Choi, Jaehun | Chul Sung, Sang | Min Kim, Han | Kyum Lee, Sang | Park, Heesung

    Sustainable Energy Technologies and Assessments, Vol. 56 (2023), Iss. P.103075

    https://doi.org/10.1016/j.seta.2023.103075 [Citations: 4]
  3. CFD Investigation of Vehicle’s Ventilation Systems and Analysis of ACH in Typical Airplanes, Cars, and Buses

    Pirouz, Behrouz | Mazzeo, Domenico | Palermo, Stefania Anna | Naghib, Seyed Navid | Turco, Michele | Piro, Patrizia

    Sustainability, Vol. 13 (2021), Iss. 12 P.6799

    https://doi.org/10.3390/su13126799 [Citations: 20]